ADDRESSABLE 4 INPUT / 4 OUTPUT MULTI-MODULE
The PY-AM-I/O-401-E Addressable 4 Input/ 4output Module is characterized as 4 inputs power limited and 4 outputs volt free relay with additional sounder circuit output. The output relay is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, autodialer to the fire brigade, BMS, etc. Also, the input circuit is used to acknowledge the normally open monitor signal from interface equipment and then send a communication signal to the control panel, ideally for monitoring the sprinkler system, pressure switch, position switch, signal valves, and other third-party equipment such as a conventional panel. In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuits of the input signal line. All interfaces can be seen on the panel and can be configured on the command builder to create requirements for fire event scenarios, as each circuit has its unique address, this module occupied 9 addresses.
The unit is manufactured based on the requirement of EN 54 part 18, European Standard. The PY-AM-I/O-401-E Module is compatible with the PY-CP-4A Analogue Intelligent Fire Alarm Control Panel, produced by single manufacturer PEPL, to avoid addressable communication compatibility problems.
Features
- LED status indicator.
- Input Cable monitored.
- One sounder circuit output.
- Four circuits 24Vdc/3A Output relay contact.
- Built-in MCU processor and digital addressing.
- Parallel connecting to 16 conventional detectors.
- Four circuits Input Fire or Supervisory signal configuration.
- Enhanced capacity of interference resistance by using a multilevel wave filtering process.
- Stock: In Stock
- Model: PY-AM-I/O-401-E
Technical Specifications
Power Rating | |
Current Consumption Standby | Standby 1.5mA, Alarm: 25mA (at 4 active relays) |
External PSU | 20 to 28VDC |
Input Voltage | Loop Power:24VDC [18V to 28V] |
Module | |
Control output voltage | 24VDC / 3A rating (per circuit) |
Dimension / LWH | 150 mm x 100 mm |
Humidity | 0 to 95% Relative Humidity, Non condensing |
Indicator Status | Normal: Single blink/Active: Steady/Fault: Double Blink |
Input Relay | 4 Circuit: Normally Open dry contact |
Input Resistance | 5.1Kohms/ ¼W |
Material / Colour | PCB |
Operating Temperature | -10°C to +50°C |
Output Relay | 4 Circuit: Normally Open/ Close dry contact |
Protocol/ Addressing | Private, Occupied 9 address |
Sounder Circuit Output | 24VDC Power Limited |
Weight | 360 g |